Low Voltage ABC Aerial Bundled Cable (JKLYJ)

China 
                                 Low Voltage ABC Aerial Bundled Cable (JKLYJ)                              Herstellung und Lieferant

Low Voltage ABC Aerial Bundled Cable (JKLYJ) image

Get Latest Price Request a quote

Basis Info

Modell Nr..
JKLYJ

Art
Isolierte

Leitertyp
Stranded

Anwendung
Oben

Leitermaterial
Aluminium

Mantelmaterial
PVC

Isoliermaterial
XLPE

Bescheinigung
ISO9001 ,
CE

Zusätzliche Informationen.

Warenzeichen
JIAPU

Verpackung
Wooden Drum

Standard
any one

Herkunft
Henan, China

HS-Code
4101962331

Produktionskapazität
5000 Kilometers/Month

Produktbeschreibung

Low Voltage ABC Aerial Bundled Cable (JKLYJ)

1. Features
RUS accepted.
Extruded ridges for easy Phase identification.

2. Standards
ICEA S-76-474
Neutral-Supported Power Cable Assemblies with Weather-Resistant Extruded Insulated rated 600V.

3. Application
For overhead distribution of electrical energy, such as a supply power, from pole-mounted transformer to the user’s service head where connection to the service entrance cable is made.
Also for temporary services and street light installations.

4. Specification
Maximum operating voltage: 600 volts, Maximum conductor operation temperatures:
Wet and dry locations:
Normal: 90° C
Emergency: 130° C
Short Circuit: 250° C

5. Engineering Information
Conductor: Aluminum alloy 1350-H19, solid conductor per ASTM B230, Compressed Class B stranding, or Class A stranding or unilay-compressed per ASTM B231, or combination unilay (19 wires)Per ASTM B786. Upon Request: Copper Conductors.
Separator: Suitable opaque tape as required.
Insulation: Black thermoset croos-linked polyethylene (XLPE). Upon request: PE insulated.
Neutral: Bare aluminum alloy 1350-H19 classes A stranding per ASTM B231 or ACSR stranding per ASTN B232, or ACSR/AW per ASTM B549. Upon request cover neutral.
Conductor Phase ID: Extruded ridges.
Duplex: Consist of one black phase insulated conductor twisted around a bare neutral conductor

Specification:

(1)Self-supporting

Phase Phase Phase Approx.Overall Diameter Max. D.C. Resistance of Conductor at 20ºC
AAC+UV-XLPE Compact Conductor UV-XLPE Insulation
No.X Normal Cross Section of Cores No.of Al Wires Overall Diameter Normal Thickness Min. Diameter
No. X mm2 mm mm mm mm mm ohm/km
1 X 10 7 4.05 1.0 0.8 6.05 6.05 3.08
1 X 16 7 4.8 1.2 0.98 7.2 7.20 1.91
1 X 25 7 6 1.2 0.98 8.4 8.40 1.20
1 X 35 7 7.0 1.4 1.16 9.8 9.80 0.868
1 X 50 7 8.3 1.4 1.16 11.1 11.10 0.641
1 X 70 19 9.8 1.4 1.16 12.6 12.60 0.443
1 X 95 19 11.6 1.6 1.34 14.8 14.80 0.320
1 X 120 19 13 1.6 1.34 16.2 16.20 0.253
1 X 150 19 14.6 1.8 1.52 18.2 18.20 0.206
1 X 185 36 16.2 2.0 1.70 20.2 20.20 0.164
1 X 240 36 18.4 2.2 1.88 22.8 22.80 0.125
2 X 10 7 4.05 1.0 0.8 6.05 12.10 3.08
2 X 16 7 4.8 1.2 0.98 7.2 14.40 1.91
2 X 25 7 6 1.2 0.98 8.4 16.80 1.20
2 X 35 7 7.0 1.4 1.16 9.8 19.60 0.868
2 X 50 7 8.3 1.4 1.16 11.1 22.20 0.641
2 X 70 19 9.8 1.4 1.16 12.6 25.20 0.443
2 X 95 19 11.6 1.6 1.34 14.8 29.60 0.320
2 X 120 19 13 1.6 1.34 16.2 32.40 0.253
2 X 150 19 14.6 1.8 1.52 18.2 36.40 0.206
2 X 185 36 16.2 2.0 1.70 20.2 40.40 0.164
2 X 240 36 18.4 2.2 1.88 22.8 45.60 0.125
3 X 10 7 4.05 1.0 0.8 6.05 13.07 3.08
3 X 16 7 4.8 1.2 0.98 7.2 15.55 1.91
3 X 25 7 6 1.2 0.98 8.4 18.14 1.20
3 X 35 7 7.0 1.4 1.16 9.8 21.17 0.868
3 X 50 7 8.3 1.4 1.16 11.1 23.98 0.641
3 X 70 19 9.8 1.4 1.16 12.6 27.22 0.443
3 X 95 19 11.6 1.6 1.34 14.8 31.97 0.320
3 X 120 19 13 1.6 1.34 16.2 34.99 0.253
3 X 150 19 14.6 1.8 1.52 18.2 39.31 0.206
3 X 185 36 16.2 2.0 1.70 20.2 43.63 0.164
3 X 240 36 18.4 2.2 1.88 22.8 49.25 0.125
4 X 10 7 4.05 1.0 0.8 6.05 14.64 3.08
4 X 16 7 4.8 1.2 0.98 7.2 17.42 1.91
4 X 25 7 6 1.2 0.98 8.4 20.33 1.20
4 X 35 7 7.0 1.4 1.16 9.8 23.72 0.868
4 X 50 7 8.3 1.4 1.16 11.1 26.86 0.641
4 X 70 19 9.8 1.4 1.16 12.6 30.49 0.443
4 X 95 19 11.6 1.6 1.34 14.8 35.82 0.320
4 X 120 19 13 1.6 1.34 16.2 39.20 0.253
4 X 150 19 14.6 1.8 1.52 18.2 44.04 0.206
4 X 185 36 16.2 2.0 1.70 20.2 48.88 0.164
4 X 240 36 18.4 2.2 1.88 22.8 55.18 0.125

(2) Phase + Neutral

Phase Neutral Phase Neutral Approx.Overall Diameter Max. D.C. Resistance of Conductor at 20ºC
AAC+UV-XLPE AAAC Compact Conductor UV-XLPE Insulation Conductor
Phase Neutral
No.X Normal Cross Section of Cores No.X Normal Cross Section of Cores No.of Al.Wire Overall Dia. Normal Thickness Min. No./Dia. of Al Alloy Wire
No. X mm2 No. X mm2 mm mm Min. No./mm mm ohm/km ohm/km
1 X 16 1 X 16 7 4.8 1.2 0.98 7/1.70 12.30 1.91 2.217
1 X 25 1 X 25 7 6 1.2 0.98 7/2.10 14.70 1.20 1.393
1 X 35 1 X 35 7 7.0 1.4 1.16 7/2.50 17.30 0.868 1.007
1 X 50 1 X 50 7 8.3 1.4 1.16 7/3.00 20.10 0.641 0.744
1 X 70 1 X 70 19 9.8 1.4 1.16 7/3.50 23.10 0.443 0.514
1 X 95 1 X 95 19 11.6 1.6 1.34 19/2.50 27.30 0.320 0.371
1 X 120 1 X 120 19 13 1.6 1.34 19/2.80 30.20 0.253 0.294
1 X 150 1 X 150 19 14.6 1.8 1.52 37/2.25 33.95 0.206 0.239
1 X 185 1 X 185 36 16.2 2.0 1.70 37/2.50 37.70 0.164 0.190
1 X 240 1 X 240 36 18.4 2.2 1.88 61/2.25 43.05 0.125 0.145
2 X 16 1 X 16 7 4.8 1.2 0.98 7/1.70 14.04 1.91 2.217
2 X 25 1 X 25 7 6 1.2 0.98 7/2.10 16.63 1.20 1.393
2 X 35 1 X 35 7 7.0 1.4 1.16 7/2.50 19.51 0.868 1.007
2 X 50 1 X 50 7 8.3 1.4 1.16 7/3.00 22.46 0.641 0.744
2 X 70 1 X 70 19 9.8 1.4 1.16 7/3.50 25.70 0.443 0.514
2 X 95 1 X 95 19 11.6 1.6 1.34 19/2.50 30.31 0.320 0.371
2 X 120 1 X 120 19 13 1.6 1.34 19/2.80 33.41 0.253 0.294
2 X 150 1 X 150 19 14.6 1.8 1.52 37/2.25 37.55 0.206 0.239
2 X 185 1 X 185 36 16.2 2.0 1.70 37/2.50 41.69 0.164 0.190
2 X 240 1 X 240 36 18.4 2.2 1.88 61/2.25 47.41 0.125 0.145
3 X 16 1 X 16 7 4.8 1.2 0.98 7/1.70 16.15 1.91 2.217
3 X 25 1 X 25 7 6 1.2 0.98 7/2.10 19.06 1.20 1.393
3 X 35 1 X 35 7 7.0 1.4 1.16 7/2.50 22.32 0.868 1.007
3 X 50 1 X 50 7 8.3 1.4 1.16 7/3.00 25.59 0.641 0.744
3 X 70 1 X 70 19 9.8 1.4 1.16 7/3.50 29.22 0.443 0.514
3 X 95 1 X 95 19 11.6 1.6 1.34 19/2.50 34.42 0.320 0.371
3 X 120 1 X 120 19 13 1.6 1.34 19/2.80 37.87 0.253 0.294
3 X 150 1 X 150 19 14.6 1.8 1.52 37/2.25 42.56 0.206 0.239
3 X 185 1 X 185 36 16.2 2.0 1.70 37/2.50 47.25 0.164 0.190
3 X 240 1 X 240 36 18.4 2.2 1.88 61/2.25 53.63 0.125 0.145

(3) Phase + Neutral + Service Connection

Phase Neutral Service Connection Phase Neutral Service Connection Approx.Overall Diameter of Bundled Cable
AAC+UV-XLPE AAAC+UV-XLPE AAC+UV-XLPE Conductor UV-XLPE Conductor UV-XLPE Compact Conductor UV-XLPE
No.X Normal Cross Section of Cores No.X Normal Cross Section of Cores No.X Normal Cross Section of Cores No. of Al. Wire Overall Dia. Normal
Thickness
No./Dia. of Al. Wire Normal
Thickness
No. of Al. Wire Overall Dia. Normal
Thickness
No. X mm2 No. X mm2 No. X mm2 mm mm mm mm No./mm mm mm mm
3 X 16 1 X 50 1 X 16 7 4.8 1.2 7/3.0 1.4 7 4.8 1.2 26.2
3 X 25 1 X 50 1 X 16 7 6 1.2 7/3.0 1.4 7 4.8 1.2 28.6
3 X 35 1 X 50 1 X 16 7 7.0 1.4 7/3.0 1.4 7 4.8 1.2 31.4
3 X 50 1 X 50 1 X 16 7 8.3 1.4 7/3.0 1.4 7 4.8 1.2 34
3 X 70 1 X 50 1 X 16 19 9.8 1.4 7/3.0 1.4 7 4.8 1.2 37
3 X 95 1 X 50 1 X 16 19 11.6 1.6 7/3.0 1.4 7 4.8 1.2 41.4
3 X 120 1 X 50 1 X 16 19 13 1.6 7/3.0 1.4 7 4.8 1.2 44.2
3 X 16 1 X 50 2 X 16 7 4.8 1.2 7/3.0 1.4 7 4.8 1.2 26.2
3 X 25 1 X 50 2 X 16 7 6 1.2 7/3.0 1.4 7 4.8 1.2 28.6
3 X 35 1 X 50 2 X 16 7 7.0 1.4 7/3.0 1.4 7 4.8 1.2 31.4
3 X 50 1 X 50 2 X 16 7 8.3 1.4 7/3.0 1.4 7 4.8 1.2 34
3 X 70 1 X 50 2 X 16 19 9.8 1.4 7/3.0 1.4 7 4.8 1.2 37
3 X 95 1 X 50 2 X 16 19 11.6 1.6 7/3.0 1.4 7 4.8 1.2 41.4
3 X 120 1 X 50 2 X 16 19 13 1.6 7/3.0 1.4 7 4.8 1.2 44.2

Wer wir sind China Low Voltage ABC Aerial Bundled Cable (JKLYJ) Herstellung und Lieferant,Sie können weitere Informationen per E-Mail erhalten, Sie erhalten einen günstigen Preis oder einen Fabrikpreis.

Get Latest Price Request a quote

Popular Aerial Cable Produkte

High Quality ABC Aerial Bundled Cable with IEC60502 Standard

ABC Overhead Aerial Bundled Cable with IEC60502 Standard

Hot Seller 0.6/1kv 25mm2/ 50mm2 Aerial Bundled Cable

0.6/1kv Aluminum Conductor XLPE Insulated ABC Cable

Hot Selling Cable Aluminium Core XLPE Insulation ABC Cable

High Performance 11kv Overhead ABC Cable

Popular jpcable99 Produkte

AAC entblössen Leiter 250sqmm 315sqmm 400sqmm aller angeschwemmte Energien-Aluminiumleiter

XLPE Insulated Power Cable

Kupferner Leiter-Gebäude-Draht

AAAC Ulme 19 verdrahtet 3.76mm mit gutem Preis BS-En50183

Einkerniges kupfernes Leiter XLPE Isolier-Belüftung-Hüllen-Energien-Kabel

Stahlband-gepanzertes Energien-Kabel (STA Kabel)

Popular Low Voltage ABC Aerial Bundled Cable (JKLYJ) Produkte

  • No related articles
  • Popular Low Voltage Aerial Bundle Cable Produkte

  • No related articles
  • Tags: , , ,

    SCHNELLER UND ZUVERLÄSSIGER SERVICE FÜR IHR PROJEKT

    Wenden Sie sich noch heute an unsere geschulten Experten, um Ihre perfekte Stromversorgungslösung zu finden.

    STELLE EINE FRAGE