22kv Medium Voltage Underground XLPE Insulated Power Cable
22kv Medium Voltage Underground XLPE Insulated Power Cable image
Get Latest Price Request a quote
Basis Info
U-Bahn
CE
Zusätzliche Informationen.
Produktbeschreibung
22kV Medium Voltage Underground XLPE Insulated Power Cable
Application:
Media Voltage XLPE Insulated power cable is used to transmit and distribute power in power transmission and distribution system of 35kV or lower. It is generally applied to the fields including power, construction, mines, metallurgy, petrochemical industry and communication in complete replace of oil immersed paper insulated power cable.
Prpperty:
1.The highest allowed operating temperature of conductor for long-term working is 90 degrees.
2.In short circuit (Max long term is no more than 5 seconds). The highest temperature for conductor is no more than 250 degrees.
3.The cable is laid without horizontal drop limit. The environment temperature should be no lower than 0 when lay. Otherwise it should be preheated.
4.Excellent electrical performance, resistance to chemical corrosion.
5.They can stand advisable traction when laid.They can stand traction from Outside.Left low smoke halogen-free after burned.Retard the burning of the cable.
Specification:
Standard:
IEC60502,designing and manufacturing special power cable according to the other standards required by the customers.
1)3.6/6(7.2)kV,3.6/6.6(7.2)kV,Single Core,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor | Normal Diameter of Conductor | Normal Thickness of Insulation | Normal Thickness of Copper Tape |
Normal Thickness of Outer Sheath | Approx. Overall Dia. |
Approx. Net Weight | Max. D.C. Resistance of Conductor at 20ºC | ||
Al Conductor | Cu Conductor | Al Conductor | Cu Conductor | ||||||
mm2 | mm | mm | mm | mm | mm | kg/m | kg/m | Ω/km | Ω/km |
25 | 6.0 | 2.5 | 0.12 | 1.5 | 17.6 | 0.34 | 0.49 | 1.2000 | 0.7270 |
35 | 7.0 | 2.5 | 0.12 | 1.5 | 18.5 | 0.39 | 0.60 | 0.8680 | 0.5240 |
50 | 8.3 | 2.5 | 0.12 | 1.6 | 20.0 | 0.46 | 0.74 | 0.6410 | 0.3870 |
70 | 9.7 | 2.5 | 0.12 | 1.6 | 21.5 | 0.55 | 0.96 | 0.4430 | 0.2680 |
95 | 11.3 | 2.5 | 0.12 | 1.7 | 23.3 | 0.66 | 1.23 | 0.3200 | 0.1930 |
120 | 13 | 2.5 | 0.12 | 1.7 | 24.8 | 0.77 | 1.48 | 0.2530 | 0.1530 |
150 | 14.6 | 2.5 | 0.12 | 1.8 | 26.4 | 0.87 | 1.77 | 0.2060 | 0.1240 |
185 | 15.9 | 2.5 | 0.12 | 1.8 | 28.1 | 1.01 | 2.13 | 0.1640 | 0.0991 |
240 | 18.3 | 2.6 | 0.12 | 1.9 | 30.9 | 1.23 | 2.71 | 0.1250 | 0.0754 |
300 | 20.4 | 2.8 | 0.12 | 2.0 | 33.6 | 1.48 | 3.32 | 0.1000 | 0.0601 |
400 | 23.2 | 3.0 | 0.12 | 2.1 | 37.0 | 1.81 | 4.16 | 0.0778 | 0.0470 |
500 | 26.4 | 3.2 | 0.12 | 2.2 | 41.1 | 2.24 | 5.27 | 0.0605 | 0.0366 |
630 | 30.1 | 3.2 | 0.12 | 2.3 | 45.0 | 2.73 | 6.62 | 0.0469 | 0.0283 |
2)6/10(12)kV,6.35/11(12)kV,Single Core,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor | Normal Diameter of Conductor | Normal Thickness of Insulation | Normal Thickness of Copper Tape |
Normal Thickness of Outer Sheath | Approx. Overall Dia. |
Approx. Net Weight | Max. D.C. Resistance of Conductor at 20ºC | |||
Al Conductor | Cu Conductor | Al Conductor | Cu Conductor | |||||||
mm2 | mm | mm | mm | mm | mm | kg/m | kg/m | Ω/km | Ω/km | |
25 | 6.0 | 3.4 | 0.12 | 1.5 | 19.4 | 0.40 | 0.55 | 1.2000 | 0.7270 | |
35 | 6.9 | 3.4 | 0.12 | 1.6 | 20.5 | 0.45 | 0.66 | 0.8680 | 0.5240 | |
50 | 8.2 | 3.4 | 0.12 | 1.6 | 21.8 | 0.52 | 0.80 | 0.6410 | 0.3870 | |
70 | 9.7 | 3.4 | 0.12 | 1.7 | 23.5 | 0.62 | 1.03 | 0.4430 | 0.2680 | |
95 | 11.3 | 3.4 | 0.12 | 1.7 | 25.1 | 0.73 | 1.30 | 0.3200 | 0.1930 | |
120 | 12.8 | 3.4 | 0.12 | 1.8 | 26.8 | 0.85 | 1.56 | 0.2530 | 0.1530 | |
150 | 14.2 | 3.4 | 0.12 | 1.8 | 28.2 | 0.95 | 1.85 | 0.2060 | 0.1240 | |
185 | 15.9 | 3.4 | 0.12 | 1.9 | 30.1 | 1.10 | 2.22 | 0.1640 | 0.0991 | |
240 | 18.3 | 3.4 | 0.12 | 2.0 | 32.7 | 1.33 | 2.80 | 0.1250 | 0.0754 | |
300 | 20.4 | 3.4 | 0.12 | 2.0 | 34.8 | 1.54 | 3.39 | 0.1000 | 0.0601 | |
400 | 23.2 | 3.4 | 0.12 | 2.2 | 38.0 | 1.87 | 4.22 | 0.0778 | 0.0470 | |
500 | 26.4 | 3.4 | 0.12 | 2.2 | 41.5 | 2.26 | 5.29 | 0.0605 | 0.0366 | |
630 | 30.1 | 3.4 | 0.12 | 2.4 | 45.6 | 2.78 | 6.67 | 0.0469 | 0.0283 |
3)8.7/10(15)kV,Single Core,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor | Normal Diameter of Conductor | Normal Thickness of Insulation | Normal Thickness of Copper Tape |
Normal Thickness of Outer Sheath | Approx. Overall Dia. |
Approx. Net Weight | Max. D.C. Resistance of Conductor at 20ºC | |||
Al Conductor | Cu Conductor | Al Conductor | Cu Conductor | |||||||
mm2 | mm | mm | mm | mm | mm | kg/m | kg/m | Ω/km | Ω/km | |
25 | 6.0 | 4.5 | 0.12 | 1.6 | 21.8 | 0.48 | 0.63 | 1.2000 | 0.7270 | |
35 | 6.9 | 4.5 | 0.12 | 1.7 | 22.9 | 0.54 | 0.75 | 0.8680 | 0.5240 | |
50 | 8.2 | 4.5 | 0.12 | 1.7 | 24.2 | 0.61 | 0.89 | 0.6410 | 0.3870 | |
70 | 9.7 | 4.5 | 0.12 | 1.8 | 25.9 | 0.72 | 1.13 | 0.4430 | 0.2680 | |
95 | 11.3 | 4.5 | 0.12 | 1.8 | 27.5 | 0.84 | 1.40 | 0.3200 | 0.1930 | |
120 | 12.8 | 4.5 | 0.12 | 1.9 | 29.2 | 0.96 | 1.67 | 0.2530 | 0.1530 | |
150 | 14.2 | 4.5 | 0.12 | 1.9 | 30.6 | 1.06 | 1.96 | 0.2060 | 0.1240 | |
185 | 15.9 | 4.5 | 0.12 | 2.0 | 32.5 | 1.22 | 2.34 | 0.1640 | 0.0991 | |
240 | 18.3 | 4.5 | 0.12 | 2.1 | 35.1 | 1.46 | 2.93 | 0.1250 | 0.0754 | |
300 | 20.4 | 4.5 | 0.12 | 2.1 | 37.2 | 1.68 | 3.52 | 0.1000 | 0.0601 | |
400 | 23.2 | 4.5 | 0.12 | 2.2 | 40.2 | 2.00 | 4.35 | 0.0778 | 0.0470 | |
500 | 26.4 | 4.5 | 0.12 | 2.3 | 43.9 | 2.43 | 5.45 | 0.0605 | 0.0366 | |
630 | 30.1 | 4.5 | 0.12 | 2.4 | 47.8 | 2.93 | 6.83 | 0.0469 | 0.0283 |
4)12/20(24)kV, 12.7/22(24)kV,Single Core,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor | Normal Diameter of Conductor | Normal Thickness of Insulation | Normal Thickness of Copper Tape |
Normal Thickness of Outer Sheath | Approx. Overall Dia. |
Approx. Net Weight | Max. D.C. Resistance of Conductor at 20ºC | ||
Al Conductor | Cu Conductor | Al Conductor | Cu Conductor | ||||||
mm2 | mm | mm | mm | mm | mm | kg/m | kg/m | Ω/km | Ω/km |
25 | |||||||||
35 | 6.9 | 5.5 | 0.12 | 1.7 | 24.9 | 0.62 | 0.83 | 0.8680 | 0.5240 |
50 | 8.2 | 5.5 | 0.12 | 1.8 | 26.4 | 0.70 | 0.98 | 0.6410 | 0.3870 |
70 | 9.7 | 5.5 | 0.12 | 1.8 | 27.9 | 0.80 | 1.21 | 0.4430 | 0.2680 |
95 | 11.3 | 5.5 | 0.12 | 1.9 | 29.7 | 0.94 | 1.50 | 0.3200 | 0.1930 |
120 | 12.8 | 5.5 | 0.12 | 1.9 | 31.2 | 1.05 | 1.77 | 0.2530 | 0.1530 |
150 | 14.2 | 5.5 | 0.12 | 2.0 | 32.8 | 1.17 | 2.07 | 0.2060 | 0.1240 |
185 | 15.9 | 5.5 | 0.12 | 2.0 | 34.5 | 1.33 | 2.45 | 0.1640 | 0.0991 |
240 | 18.3 | 5.5 | 0.12 | 2.1 | 37.1 | 1.57 | 3.04 | 0.1250 | 0.0754 |
300 | 20.4 | 5.5 | 0.12 | 2.2 | 39.4 | 1.81 | 3.66 | 0.1000 | 0.0601 |
400 | 23.2 | 5.5 | 0.12 | 2.3 | 42.4 | 2.14 | 4.49 | 0.0778 | 0.0470 |
500 | 26.4 | 5.5 | 0.12 | 2.4 | 46.1 | 2.58 | 5.61 | 0.0605 | 0.0366 |
630 | 30.1 | 5.5 | 0.12 | 2.4 | 49.8 | 3.10 | 6.99 | 0.0469 | 0.0283 |
5)18/30(36)kV,19/33(36)kV,Single Core,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor | Normal Diameter of Conductor | Normal Thickness of Insulation | Normal Thickness of Copper Tape |
Normal Thickness of Outer Sheath | Approx. Overall Dia. |
Approx. Net Weight | Max. D.C. Resistance of Conductor at 20ºC | |||
Al Conductor | Cu Conductor | Al Conductor | Cu Conductor | |||||||
mm2 | mm | mm | mm | mm | mm | kg/m | kg/m | Ω/km | Ω/km | |
25 | ||||||||||
35 | ||||||||||
50 | 8.2 | 8.0 | 0.12 | 2.0 | 31.8 | 0.95 | 1.23 | 0.6410 | 0.3870 | |
70 | 9.7 | 8.0 | 0.12 | 2.0 | 33.3 | 1.07 | 1.47 | 0.4430 | 0.2680 | |
95 | 11.3 | 8.0 | 0.12 | 2.1 | 35.1 | 1.21 | 1.78 | 0.3200 | 0.1930 | |
120 | 12.8 | 8.0 | 0.12 | 2.1 | 36.6 | 1.34 | 2.05 | 0.2530 | 0.1530 | |
150 | 14.2 | 8.0 | 0.12 | 2.2 | 38.2 | 1.47 | 2.37 | 0.2060 | 0.1240 | |
185 | 15.9 | 8.0 | 0.12 | 2.2 | 39.9 | 1.64 | 2.76 | 0.1640 | 0.0991 | |
240 | 18.3 | 8.0 | 0.12 | 2.3 | 42.5 | 1.90 | 3.37 | 0.1250 | 0.0754 | |
300 | 20.4 | 8.0 | 0.12 | 2.4 | 44.8 | 2.16 | 4.01 | 0.1000 | 0.0601 | |
400 | 23.2 | 8.0 | 0.12 | 2.4 | 47.6 | 2.52 | 4.87 | 0.0778 | 0.0470 | |
500 | 26.4 | 8.0 | 0.12 | 2.5 | 51.3 | 2.98 | 6.01 | 0.0605 | 0.0366 | |
630 | 30.1 | 8.0 | 0.12 | 2.6 | 55.2 | 3.54 | 7.43 | 0.0469 | 0.0283 |
6)3.6/6(7.2)kV,3.6/6.6(7.2)kV,Three Cores,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor | Normal Diameter of Conductor | Normal Thickness of Insulation | Normal Thickness of Copper Tape |
Normal Thickness of Outer Sheath | Approx. Overall Dia. |
Approx. Net Weight | Max. D.C. Resistance of Conductor at 20ºC | ||||
Al Conductor | Cu Conductor | Al Conductor | Cu Conductor | ||||||||
mm2 | mm | mm | mm | mm | mm | kg/m | kg/m | Ω/km | Ω/km | ||
25 | 6.0 | 2.5 | 0.1 | 2.0 | 34.6 | 1.13 | 1.58 | 1.2000 | 0.7270 | ||
35 | 6.9 | 2.5 | 0.1 | 2.1 | 36.8 | 1.29 | 1.92 | 0.8680 | 0.5240 | ||
50 | 8.2 | 2.5 | 0.1 | 2.2 | 39.8 | 1.51 | 2.36 | 0.6410 | 0.3870 | ||
70 | 9.7 | 2.5 | 0.1 | 2.3 | 43.2 | 1.81 | 3.04 | 0.4430 | 0.2680 | ||
95 | 11.3 | 2.5 | 0.1 | 2.4 | 46.9 | 2.17 | 3.87 | 0.3200 | 0.1930 | ||
120 | 12.8 | 2.5 | 0.1 | 2.4 | 50.1 | 2.53 | 4.69 | 0.2530 | 0.1530 | ||
150 | 14.2 | 2.5 | 0.1 | 2.5 | 53.3 | 2.90 | 5.60 | 0.2060 | 0.1240 | ||
185 | 15.9 | 2.5 | 0.1 | 2.6 | 57.2 | 3.40 | 6.77 | 0.1640 | 0.0991 | ||
240 | 18.3 | 2.6 | 0.1 | 2.8 | 63.2 | 4.12 | 8.55 | 0.1250 | 0.0754 | ||
300 | 20.4 | 2.8 | 0.1 | 3.0 | 69.0 | 4.89 | 10.46 | 0.1000 | 0.0601 | ||
400 | 23.2 | 3.0 | 0.1 | 3.4 | 76.7 | 6.10 | 13.18 | 0.0778 | 0.0470 | ||
500 | 26.4 | 3.2 | 0.1 | 3.6 | 85.7 | 8.10 | 16.55 | 0.0605 | 0.0366 |
7)6/10(12)kV,6.35/11(12)kV,Three Cores,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor | Normal Diameter of Conductor | Normal Thickness of Insulation | Normal Thickness of Copper Tape |
Normal Thickness of Outer Sheath | Approx. Overall Dia. |
Approx. Net Weight | Max. D.C. Resistance of Conductor at 20ºC | |||
Al Conductor | Cu Conductor | Al Conductor | Cu Conductor | |||||||
mm2 | mm | mm | mm | mm | mm | kg/m | kg/m | Ω/km | Ω/km | |
25 | 6.0 | 3.4 | 0.1 | 2.1 | 38.7 | 1.30 | 1.75 | 1.2000 | 0.7270 | |
35 | 6.9 | 3.4 | 0.1 | 2.2 | 40.9 | 1.47 | 2.22 | 0.8680 | 0.5240 | |
50 | 8.2 | 3.4 | 0.1 | 2.3 | 43.9 | 1.70 | 2.50 | 0.6410 | 0.3870 | |
70 | 9.7 | 3.4 | 0.1 | 2.4 | 47.3 | 2.02 | 3.25 | 0.4430 | 0.2680 | |
95 | 11.3 | 3.4 | 0.1 | 2.5 | 51.0 | 2.42 | 4.12 | 0.3200 | 0.1930 | |
120 | 12.8 | 3.4 | 0.1 | 2.6 | 54.4 | 2.79 | 4.95 | 0.2530 | 0.1530 | |
150 | 14.2 | 3.4 | 0.1 | 2.7 | 57.6 | 3.17 | 5.87 | 0.2060 | 0.1240 | |
185 | 15.9 | 3.4 | 0.1 | 2.8 | 61.5 | 3.69 | 7.06 | 0.1640 | 0.0991 | |
240 | 18.3 | 3.4 | 0.1 | 2.9 | 66.9 | 4.38 | 8.82 | 0.1250 | 0.0754 | |
300 | 20.4 | 3.4 | 0.1 | 3.1 | 71.8 | 5.11 | 10.68 | 0.1000 | 0.0601 | |
400 | 23.2 | 3.4 | 0.1 | 3.3 | 78.3 | 6.24 | 13.32 | 0.0778 | 0.0470 | |
500 | 26.4 | 3.4 | 0.1 | 3.5 | 86.4 | 7.63 | 16.50 | 0.0605 | 0.0366 |
8)8.7/10(15)kV,Three Cores,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor | Normal Diameter of Conductor | Normal Thickness of Insulation | Normal Thickness of Copper Tape |
Normal Thickness of Outer Sheath | Approx. Overall Dia. |
Approx. Net Weight | Max. D.C. Resistance of Conductor at 20ºC | ||||
Al Conductor | Cu Conductor | Al Conductor | Cu Conductor | ||||||||
mm2 | mm | mm | mm | mm | mm | kg/m | kg/m | Ω/km | Ω/km | ||
25 | 6.0 | 4.5 | 0.1 | 2.3 | 43.9 | 1.57 | 2.02 | 0.9270 | 0.7270 | ||
35 | 6.9 | 4.5 | 0.1 | 2.4 | 46.0 | 1.75 | 2.38 | 0.6680 | 0.5240 | ||
50 | 8.2 | 4.5 | 0.1 | 2.4 | 48.8 | 2.00 | 2.85 | 0.4936 | 0.3870 | ||
70 | 9.7 | 4.5 | 0.1 | 2.5 | 52.3 | 2.34 | 3.57 | 0.3420 | 0.2680 | ||
95 | 11.3 | 4.5 | 0.1 | 2.6 | 55.9 | 2.75 | 4.45 | 0.2464 | 0.1930 | ||
120 | 12.8 | 4.5 | 0.1 | 2.7 | 59.4 | 3.16 | 5.32 | 0.1955 | 0.1530 | ||
150 | 14.2 | 4.5 | 0.1 | 2.8 | 62.6 | 3.57 | 6.27 | 0.1587 | 0.1240 | ||
185 | 15.9 | 4.5 | 0.1 | 2.9 | 66.4 | 4.07 | 7.45 | 0.1271 | 0.0991 | ||
240 | 18.3 | 4.5 | 0.1 | 3.1 | 72.0 | 4.82 | 9.25 | 0.0976 | 0.0754 | ||
300 | 20.4 | 4.5 | 0.1 | 3.3 | 77.0 | 5.71 | 11.28 | 0.0778 | 0.0601 | ||
400 | 23.2 | 4.5 | 0.1 | 3.4 | 83.2 | 6.78 | 13.86 | 0.0615 | 0.0470 | ||
500 | 26.4 | 4.5 | 0.1 | 3.5 | 91.1 | 8.20 | 17.32 | 0.0487 | 0.0366 |
9)12/20(24)kV, 12.7/22(24)kV,Three Cores,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor | Normal Diameter of Conductor | Normal Thickness of Insulation | Normal Thickness of Copper Tape |
Normal Thickness of Outer Sheath | Approx. Overall Dia. |
Approx. Net Weight | Max. D.C. Resistance of Conductor at 20ºC | ||||
Al Conductor | Cu Conductor | Al Conductor | Cu Conductor | ||||||||
mm2 | mm | mm | mm2 | mm | mm | kg/m | kg/m | Ω/km | Ω/km | ||
25 | – | ||||||||||
35 | 6.9 | 5.5 | 0.1 | 2.4 | 50.3 | 2.00 | 2.63 | 0.8680 | 0.6680 | ||
50 | 8.2 | 5.5 | 0.1 | 2.5 | 53.3 | 2.26 | 3.11 | 0.6410 | 0.4936 | ||
70 | 9.7 | 5.5 | 0.1 | 2.6 | 56.8 | 2.62 | 3.85 | 0.4430 | 0.3420 | ||
95 | 11.3 | 5.5 | 0.1 | 2.8 | 60.6 | 3.07 | 4.77 | 0.3200 | 0.2464 | ||
120 | 12.8 | 5.5 | 0.1 | 2.9 | 64.1 | 3.49 | 5.65 | 0.2530 | 0.1955 | ||
150 | 14.2 | 5.5 | 0.1 | 3.0 | 67.3 | 3.91 | 6.61 | 0.2060 | 0.1587 | ||
185 | 15.9 | 5.5 | 0.1 | 3.1 | 71.2 | 4.44 | 7.81 | 0.1640 | 0.1271 | ||
240 | 18.3 | 5.5 | 0.1 | 3.3 | 76.8 | 5.21 | 9.64 | 0.1250 | 0.0976 | ||
300 | 20.4 | 5.5 | 0.1 | 3.3 | 81.3 | 6.10 | 11.66 | 0.1000 | 0.0778 | ||
400 | 23.2 | 5.5 | 0.1 | 3.5 | 87.7 | 7.20 | 14.28 | 0.0778 | 0.0615 | ||
500 | 26.4 | 5.5 | 0.1 | 3.8 | 96.0 | 9.15 | 17.80 | 0.0605 | 0.0487 |
10)18/30(36)kV,19/33(36)kV,Three Cores,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor | Normal Diameter of Conductor | Normal Thickness of Insulation | Normal Thickness of Copper Tape |
Normal Thickness of Outer Sheath | Approx. Overall Dia. |
Approx. Net Weight | Max. D.C. Resistance of Conductor at 20ºC | ||
Al Conductor | Cu Conductor | Al Conductor | Cu Conductor | ||||||
mm2 | mm | mm | mm | mm | mm | kg/m | kg/m | Ω/km | Ω/km |
25 | |||||||||
35 | |||||||||
50 | 8.2 | 8.0 | 0.1 | 2.9 | 64.9 | 3.02 | 3.87 | 0.6410 | 0.4936 |
70 | 9.7 | 8.0 | 0.1 | 3.0 | 68.4 | 3.42 | 4.65 | 0.4430 | 0.3420 |
95 | 11.3 | 8.0 | 0.1 | 3.1 | 72.0 | 3.89 | 5.59 | 0.3200 | 0.2464 |
120 | 12.8 | 8.0 | 0.1 | 3.3 | 75.7 | 4.39 | 6.54 | 0.2530 | 0.1955 |
150 | 14.2 | 8.0 | 0.1 | 3.3 | 78.7 | 4.85 | 7.55 | 0.2060 | 0.1587 |
185 | 15.9 | 8.0 | 0.1 | 3.4 | 82.6 | 5.42 | 8.79 | 0.1640 | 0.1271 |
240 | 18.3 | 8.0 | 0.1 | 3.5 | 88.0 | 6.22 | 10.66 | 0.1250 | 0.0976 |
300 | 20.4 | 8.0 | 0.1 | 3.7 | 92.9 | 7.20 | 12.77 | 0.1000 | 0.0778 |
400 | 23.2 | 8.0 | 0.1 | 3.9 | 99.3 | 8.38 | 15.46 | 0.0778 | 0.0615 |
500 | 26.4 | 8.0 | 0.1 | 4.2 | 107.6 | 10.15 | 18.85 | 0.0605 | 0.0487 |
Wer wir sind China 22kv Medium Voltage Underground XLPE Insulated Power Cable Herstellung und Lieferant,Sie können weitere Informationen per E-Mail erhalten, Sie erhalten einen günstigen Preis oder einen Fabrikpreis.
Get Latest Price Request a quote
Popular 22kv Medium Voltage Underground XLPE Insulated Power Cable Produkte
Popular jpcable99 Produkte
Kupferner Leiter-Kurbelgehäuse-Belüftung Isolierdraht 0.5mm2 0.75mm2 1mm2
Aufbauender elektrischer Draht (H07RN) - 2
Kabel-gute Qualitätsflachdraht Kurbelgehäuse-Belüftung Henan-Jiapu isolierte
Obenliegendes AAC, AAAC, ACSR ASTM blank Standarddrähte, Energien-Kabel, aller Aluminiumleiter
Wärme Reistant kupferne Energie Isolierdrähte dem Leiter an der Energien-90c
Popular Underground Power Cable Produkte
Popular XLPE power Cable Produkte
Dreiadriges unterirdisches XLPE-Netzkabel (1~35kV)
Millivolt 11kv Copper Cable, XLPE Power Cable
Copper Conductor XLPE 5X10 Power Cable
35mm Copper PVC Insulated Electrical Power Cable
0.6/1kv Cu/XLPE/Swa/PVC Power Cable with IEC Certificate
Copper Wire High Quality Yjv Electrical Wire Power Cable
Tags: 22kv Medium Voltage Underground XLPE Insulated Power Cable, jpcable99, Underground Power Cable, XLPE power Cable