APPLICATION
Medium voltage Aerial bundled cables are mainly used for secondary overhead lines on poles or as feeders
to residential premises.
STANDARDS
Basic design to IEC 60502 / AS/NZS 3599-1 standards
CABLE CONSTRUCTION
Phase Conductor: Circular compacted stranded H68 aluminium to BS2627.
Conductor Screen: Extruded semi-conductive layer.
insulation: XLPE.
insulation Screen: Extruded semi-conductive layer.
metallic Screen(optional): Copper wire screen or copper tape screen.
Separator: Semi-conductive swellable tape.
outer Sheath: HDPE.
Support Conductor: Galvanized steel wires.
Assembly: Three XLPE insulated screened cores are bundled around the galvanized steel
wires in a right hand lay.
Construction Parameters
IEC 60502 6.35/11 kV ABC for Overhead Distribution Lines
Number of Cores xNominal Cross Section |
Phase Conductor | Messenger Suspension Unit | Continuous current rating at 300C ambient temp |
||||
Stranding | Nominal Sectional Area |
Maximum Conductor Resistance |
Stranding | Nominal Sectional Area |
Breaking Load |
||
No.×mm² | No.×mm | mm² | Ω/Km | No.×mm | mm² | KN | A |
3X50 + 1X25 | 19/1.78 | 50 | 0.641 | 7/3.0 | 50 | 60 | 116 |
3X70 + 1X50 | 19/.14 | 70 | 0.443 | 7/3.15 | 50 | 62 | 210 |
3X95+ 1X50 | 19/2.52 | 95 | 0.32 | 7/3.0 | 50 | 60 | 173 |
3X185+1X120 | 37/2.52 | 185 | 0.164 | 7/4.67 | 120 | 150 | 259 |
3X150 +1X50 | 37/2.25 | 150 | 0.206 | 7/3.15 | 50 | 62 | 365 |
3X240 +1X50 | 61/2.25 | 240 | 0.125 | 7/3.15 | 50 | 62 | 500 |
Other cross-sections can be offered upon request.
IEC 60502 19/33 kV ABC for Overhead Distribution Lines
Number of Cores xNominal Cross Section |
Phase Conductor | Messenger Suspension Unit | Continuous current rating at 300C ambient temp |
||||
Stranding | Nominal Sectional Area |
Maximum Conductor Resistance |
Stranding | Nominal Sectional Area |
Breaking Load |
||
No.×mm² | No.×mm | mm² | Ω/Km | No.×mm | mm² | KN | A |
3X50 + 1X50 | 19/1.78 | 50 | 0.641 | 7/3.0 | 50 | 60 | 165 |
3X150+ 1X50 | 37/2.25 | 150 | 0.206 | 7/3.0 | 50 | 60 | 315 |
3X185+1X70 | 37/2.52 | 185 | 0.164 | 7/3.57 | 70 | 91 | 355 |
3X70 +1X50 | 19/2.14 | 7 | 0.443 | 7/3.15 | 50 | 62 | 250 |
3X150 +1X50 | 37/2.25 | 150 | 0.206 | 7/3.15 | 50 | 62 | 370 |
Other cross-sections can be offered upon request.
AS/NZS 3599 Part 1 6.35/11 kV AL/XLPE /HDPE Non-screened Cables
Number of Cores xNominal Cross Section |
Phase Conductor | Messenger Suspension Unit |
Nominal Sectional Area | Breaking Load |
|||
Diameter of Conductor |
Thickness of Insulation |
Thickness of Insulation Screen |
Thickness of Sheath |
Stranding | |||
No.×mm² | mm | mm | mm | mm | No.×mm | mm² | KN |
3×35 | 6.9 | 3.4 | 0.8 | 1.2 | 7/4.75 | 52.4 | 1370 |
3×50 | 8.1 | 3.4 | 0.8 | 1.2 | 7/4.75 | 54.6 | 1530 |
3×70 | 9.7 | 3.4 | 0.8 | 1.2 | 7/4.75 | 57.8 | 1790 |
3×95 | 11.4 | 3.4 | 0.8 | 1.2 | 7/4.75 | 61.3 | 2100 |
3×120 | 12.8 | 3.4 | 0.8 | 1.2 | 19/3.50 | 67.3 | 2540 |
3×150 | 14.2 | 3.4 | 0.8 | 1.2 | 19/3.50 | 70.1 | 2840 |
3×185 | 15.7 | 3.4 | 0.8 | 1.2 | 19/3.50 | 73.1 | 3190 |
Other cross-sections can be offered upon request.
AS/NZS 3599 Part 1 6.35/11 kV AL/XLPE /CWS/HDPE Screened Cables
Number of Cores xNominal Cross Section |
Diameter of Conductor |
Thickness of Insulation |
Thickness of Insulation Screen |
Copper Wire Screen Stranding |
Thickness of Sheath |
Galvanized Steel Wire Stranding | Nominal Sectional Area | Breaking Load |
No.×mm² | mm | mm | mm | No.×mm | mm | No.×mm | mm² | KN |
Light Duty Screen | ||||||||
3×35 | 6.9 | 3.4 | 0.8 | 25/0.85 | 1.8 | 7/2.00 | 54.1 | 1820 |
3×35 | 6.9 | 3.4 | 0.8 | 25/0.85 | 1.8 | 19/2.00 | 58.1 | 2130 |
3×50 | 8.1 | 3.4 | 0.8 | 25/0.85 | 1.8 | 19/2.00 | 60.4 | 2300 |
3×70 | 9.7 | 3.4 | 0.8 | 25/0.85 | 1.8 | 19/2.00 | 63.6 | 2570 |
3×95 | 11.4 | 3.4 | 0.8 | 25/0.85 | 1.8 | 19/2.00 | 67.0 | 2900 |
3×120 | 12.8 | 3.4 | 0.8 | 25/0.85 | 1.8 | 19/2.00 | 69.8 | 3190 |
3×150 | 14.2 | 3.4 | 0.8 | 25/0.85 | 1.9 | 19/2.00 | 73.0 | 3530 |
3×185 | 15.7 | 3.4 | 0.8 | 25/0.85 | 1.9 | 19/2.00 | 76.0 | 3890 |
Heavy Duty Screen | ||||||||
3×35 | 6.9 | 3.4 | 0.8 | 40/0.85 | 1.8 | 7/2.00 | 54.1 | 2050 |
3×35 | 6.9 | 3.4 | 0.8 | 40/0.85 | 1.8 | 19/2.00 | 58.1 | 2360 |
3×50 | 8.1 | 3.4 | 0.8 | 23/1.35 | 1.8 | 19/2.00 | 62.4 | 2820 |
3×70 | 9.7 | 3.4 | 0.8 | 32/1.35 | 1.8 | 19/2.00 | 65.6 | 3440 |
3×95 | 11.4 | 3.4 | 0.8 | 39/1.35 | 1.8 | 19/2.00 | 69.0 | 4030 |
3×120 | 12.8 | 3.4 | 0.8 | 39/1.35 | 1.8 | 19/2.00 | 71.8 | 4320 |
3×150 | 14.2 | 3.4 | 0.8 | 39/1.35 | 1.9 | 19/2.00 | 75.0 | 4670 |
3×185 | 15.7 | 3.4 | 0.8 | 39/1.35 | 1.9 | 19/2.00 | 78.0 | 5020 |
Other cross-sections can be offered upon request.
AS/NZS 3599 Part 1 12.7/22 kV AL/XLPE /HDPE Non-screened Cables
Number of Cores xNominal Cross Section |
Phase Conductor | Messenger Suspension Unit |
Nominal Sectional Area | Breaking Load |
|||
Diameter of Conductor |
Thickness of Insulation |
Thickness of Insulation Screen |
Thickness of Sheath |
Stranding | |||
No.×mm² | mm | mm | mm | mm | No.×mm | mm² | KN |
3×35 | 6.9 | 5.5 | 0.8 | 1.2 | 7/4.75 | 61.0 | 1780 |
3×50 | 8.1 | 5.5 | 0.8 | 1.2 | 7/4.75 | 63.3 | 1970 |
3×70 | 9.7 | 5.5 | 0.8 | 1.2 | 7/4.75 | 66.5 | 2260 |
3×95 | 11.4 | 5.5 | 0.8 | 1.2 | 7/4.75 | 69.9 | 2600 |
3×120 | 12.8 | 5.5 | 0.8 | 1.2 | 19/3.50 | 75.9 | 3070 |
3×150 | 14.2 | 5.5 | 0.8 | 1.2 | 19/3.50 | 78.7 | 3390 |
3×185 | 15.7 | 5.5 | 0.8 | 1.2 | 19/3.50 | 81.7 | 3760 |
Other cross-sections can be offered upon request.
AS/NZS 3599 Part 1 12.7/22 kV AL/XLPE /CWS/HDPE Screened Cables
Number of Cores xNominal Cross Section |
Diameter of Conductor |
Thickness of Insulation |
Thickness of Insulation Screen |
Copper Wire Screen Stranding |
Thickness of Sheath |
Galvanized Steel Wire Stranding |
Nominal Sectional Area |
Breaking Load |
No.×mm² | mm | mm | mm | No.×mm | mm | No.×mm | mm² | KN |
Light Duty Screen | ||||||||
3×35 | 6.9 | 5.5 | 0.8 | 25/0.85 | 1.8 | 7/2.00 | 62.7 | 2280 |
3×35 | 6.9 | 5.5 | 0.8 | 25/0.85 | 1.8 | 19/2.00 | 66.7 | 2580 |
3×50 | 8.1 | 5.5 | 0.8 | 25/0.85 | 1.8 | 19/2.00 | 69.0 | 2780 |
3×70 | 9.7 | 5.5 | 0.8 | 25/0.85 | 1.9 | 19/2.00 | 72.6 | 3110 |
3×95 | 11.4 | 5.5 | 0.8 | 25/0.85 | 1.9 | 19/2.00 | 76.0 | 3460 |
3×120 | 12.8 | 5.5 | 0.8 | 25/0.85 | 2.0 | 19/2.00 | 79.2 | 3810 |
3×150 | 14.2 | 5.5 | 1.0 | 25/0.85 | 2.0 | 19/2.00 | 82.8 | 4230 |
3×185 | 15.7 | 5.5 | 1.0 | 25/0.85 | 2.1 | 19/2.00 | 86.2 | 4650 |
Heavy Duty Screen | ||||||||
3×35 | 6.9 | 5.5 | 0.8 | 40/0.85 | 1.8 | 7/2.00 | 62.7 | 2510 |
3×35 | 6.9 | 5.5 | 0.8 | 40/0.85 | 1.8 | 19/2.00 | 66.7 | 2810 |
3×50 | 8.1 | 5.5 | 0.8 | 23/1.35 | 1.8 | 19/2.00 | 71.0 | 3300 |
3×70 | 9.7 | 5.5 | 0.8 | 32/1.35 | 1.9 | 19/2.00 | 74.6 | 3970 |
3×95 | 11.4 | 5.5 | 0.8 | 39/1.35 | 1.9 | 19/2.00 | 78.0 | 4600 |
3×120 | 12.8 | 5.5 | 0.8 | 39/1.35 | 2.0 | 19/2.00 | 81.2 | 4950 |
3×150 | 14.2 | 5.5 | 1.0 | 39/1.35 | 2.0 | 19/2.00 | 84.8 | 5360 |
3×185 | 15.7 | 5.5 | 1.0 | 39/1.35 | 2.1 | 19/2.00 | 88.2 | 5790 |
Other cross-sections can be offered upon request.
Technical Data
Nominal Cross Section |
Continuous Current Rating | ||
Still air | 1m/s wind | 2m/s wind | |
mm² | A | A | A |
35 | 105 | 145 | 165 |
50 | 125 | 170 | 200 |
70 | 150 | 215 | 250 |
95 | 180 | 260 | 300 |
120 | 205 | 300 | 350 |
150 | 230 | 340 | 395 |
185 | 265 | 390 | 450 |
Wer wir sind China MV-Antenne, Gebündelter Leiter, ABC-Kabel, Stromverteilung Über Kopf Herstellung und Lieferant,Sie können weitere Informationen per E-Mail erhalten, Sie erhalten einen günstigen Preis oder einen Fabrikpreis.
Get Latest Price Request a quote
Popular abc-kabel Produkte
Kabelübertragung und Distrubiton Zeile ABC-Luftbündel-Kabel-obenliegendes Niederspannungs-Kabel
0,6/1kV Overhead-Kabel-Overhead Aluminium Service Drop Wire Aerial Bundle Kabel Für Freileitung
XLPE Isolier-ABC-Kabel 2*35mm2
Aerail rollte das ABC-Kabel-Service-Transceiverkabel zusammen (Quadruplex)
Triplex Service Drop ACSR Neutralleiter Zuzara
Neuer Markenservice für PVC/XLPE/PE-isolierte AAC/ACSR/AAAAC-Leiterdoppelleitung Stichleitung
Popular Gebündelter Leiter Produkte
4-adriges ABC-Kabel, Antennenkabel, gebündelter Leiter
Popular huatongcable Produkte
8 AWG Kupferleiter PVC-Isolierte Nylon-Jacke Thhn-Draht 600 V
XLPE-Isoliertes Stahlband-Gepanzertes Netzkabel
Overhead Triplex Service Drop Halotis Luftbündelkabel für Übertragungsleitung
Oberleitung Stromübertragungsleitung ACSR
1,5 mm Elektrokabel PVC-Gebäudedraht Elektrokabel aus Kupfer
Oberleiter Aluminiumleiter Stahl Verstärkt ACSR-Leiter
Popular Millivolt-zusammengerollter Luftleiter Produkte
Millivolt-zusammengerollte Leiter ABC-obenliegende Kabel-Verteilungs-Luftzeile
Tags: abc-kabel, Gebündelter Leiter, huatongcable, Millivolt-zusammengerollter Luftleiter, MV-Antenne, Stromverteilung Über Kopf