Primary Ud Cable, 35 Kv, Al/Epr/Neutral/LLDPE (AEIC CS 8/ICEA S-94-649)
Primary Ud Cable, 35 Kv, Al/Epr/Neutral/LLDPE (AEIC CS 8/ICEA S-94-649) image
Get Latest Price Request a quote
Basis Info
CCC
Zusätzliche Informationen.
Produktbeschreibung
Primary UD Cable, 35 KV, Al/EPR/Neutral/LLDPE (AEIC CS 8/ICEA S-94-649)
Applications:
Predominantly used for primary underground distribution; Suitable for use in wet or dry locations, direct burial, underground duct, and where exposed to sunlight. To be used at 15, 000 volts or less and at conductor temperatures not to exceed 90° C for normal operation.
Specifications:
Primary UD Cable meets or exceeds the following ASTM specifications:
B-3 Soft Annealed Copper Wire.
B-8 Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard or Soft.
B-230 Aluminum, 1350-H19 Wire for Electrical Purposes.
B-231 Aluminum 1350 Conductors, Concentric-Lay-Stranded.
B-609 Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes.
Primary UD Cable is manufactured to the latest edition of the following specifications, and in case of specification conflicts, in the order listed:
ANSI/ICEA S-94-649
AEIC CS-8
RUS U-1
Construction:
The phase conductor is concentrically stranded, compressed soft copper or 1350-H16/26 aluminum alloy. The cable is composed of the conductor with moisture block in the strands, covered by a semi-conducting cross-linked polyethylene strand shield, an ethylene propylene rubber primary insulation, and a semi-conducting cross-linked polyethylene insulation shield. Conductors are available with either 100% or 133% insulation levels. A concentric neutral of bare copper wires and an insulating polyethylene jacket is applied over the insulation shield. The cable is identified by surface print on the jacket and with the lightning bolt symbol for supply cables indented in the jacket. A semi-conducting polyethylene jacket is available upon request.
Maximum Conductor Normal Operation: – 90O C;
Emergency Overload: – 130O C
Temperatures: Short Circuit – 250 C
Application: Medium voltage power cable for single phase underground distribution (UD), including getaway systems in low profile substations. Application:
Features: 1. Simultaneous extrusion of strand shield, insulation, and insulation shield (triple extrusion, dry curing process) forms a virtually perfect cable core, eliminating unequal electrical stress.
2. Ethylene Propylene Rubber (EPR) insulation offers: Excellent heat, moisture and corona resistance; Electrical stability under stress; Low dielectric loss, chemical resistance.
1/3 Neutral | Full Neutral | ||||||||||||||
Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation in | Number of Wires | Size AWG | Jacket Thickness mil | Approximate Outside Diameter in | Approximate Net Weight lb/kft | Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation in | Number of Wires | Size AWG | Jacket Thickness mil | Approximate Outside Diameter in | Approximate Net Weight lb/kft |
Aluminum 100% Insulation Level (345 mil) | |||||||||||||||
1/0 | 1 | 1.06 | 6 | 14 | 50 | 1.38 | 858 | 1/0 | 1 | 1.06 | 16 | 14 | 50 | 1.38 | 979 |
1/0 | 19 | 1.10 | 6 | 14 | 50 | 1.42 | 895 | 1/0 | 19 | 1.10 | 16 | 14 | 50 | 1.42 | 1015 |
2/0 | 19 | 1.14 | 7 | 14 | 50 | 1.47 | 971 | 2/0 | 19 | 1.14 | 20 | 14 | 50 | 1.47 | 1127 |
3/0 | 19 | 1.19 | 9 | 14 | 50 | 1.52 | 1070 | 2/0 | 19 | 1.14 | 13 | 12 | 50 | 1.50 | 1167 |
4/0 | 19 | 1.25 | 11 | 14 | 50 | 1.57 | 1184 | 3/0 | 19 | 1.19 | 25 | 14 | 50 | 1.52 | 1263 |
250 | 37 | 1.30 | 13 | 14 | 80 | 1.69 | 1358 | 3/0 | 19 | 1.19 | 16 | 12 | 50 | 1.55 | 1300 |
350 | 37 | 1.40 | 18 | 14 | 80 | 1.79 | 1604 | 4/0 | 19 | 1.25 | 32 | 14 | 50 | 1.57 | 1437 |
500 | 37 | 1.53 | 25 | 14 | 80 | 1.95 | 1989 | 4/0 | 19 | 1.25 | 20 | 12 | 50 | 1.61 | 1468 |
500 | 37 | 1.53 | 16 | 12 | 80 | 1.99 | 2036 | 4/0 | 19 | 1.25 | 13 | 10 | 80 | 1.71 | 1592 |
750 | 61 | 1.74 | 24 | 12 | 80 | 2.19 | 2628 | 250 | 37 | 1.30 | 25 | 12 | 80 | 1.73 | 1716 |
750 | 61 | 1.74 | 15 | 10 | 80 | 2.24 | 2684 | 250 | 37 | 1.30 | 16 | 10 | 80 | 1.77 | 1772 |
1000 | 61 | 1.89 | 31 | 12 | 80 | 2.34 | 3139 | 350 | 37 | 1.40 | 32 | 12 | 80 | 1.83 | 2038 |
1000 | 61 | 1.89 | 20 | 10 | 80 | 2.38 | 3217 | 350 | 37 | 1.40 | 20 | 10 | 80 | 1.87 | 2084 |
1000 | 61 | 1.89 | 16 | 9 | 80 | 2.41 | 3260 | 350 | 37 | 1.40 | 16 | 9 | 80 | 1.89 | 2119 |
– | – | – | – | – | – | – | – | 500 | 37 | 1.53 | 29 | 10 | 80 | 2.03 | 2667 |
– | – | – | – | – | – | – | – | 750 | 61 | 1.74 | 28 | 8 | 80 | 2.29 | 3661 |
– | – | – | – | – | – | – | – | 1000 | 61 | 1.89 | 37 | 8 | 80 | 2.44 | 4483 |
Aluminum 133% Insulation Level (420 mil) | |||||||||||||||
1/0 | 19 | 1.25 | 6 | 14 | 50 | 1.57 | 1076 | 1/0 | 19 | 1.25 | 16 | 14 | 50 | 1.57 | 1196 |
2/0 | 19 | 1.29 | 7 | 14 | 50 | 1.62 | 1157 | 2/0 | 19 | 1.29 | 20 | 14 | 80 | 1.68 | 1380 |
3/0 | 19 | 1.34 | 9 | 14 | 80 | 1.73 | 1331 | 2/0 | 19 | 1.29 | 13 | 12 | 80 | 1.71 | 1424 |
4/0 | 19 | 1.40 | 11 | 14 | 80 | 1.79 | 1454 | 3/0 | 19 | 1.34 | 25 | 14 | 80 | 1.73 | 1524 |
250 | 37 | 1.45 | 13 | 14 | 80 | 1.84 | 1571 | 3/0 | 19 | 1.34 | 16 | 12 | 80 | 1.76 | 1566 |
350 | 37 | 1.56 | 18 | 14 | 80 | 1.98 | 1876 | 4/0 | 19 | 1.40 | 32 | 14 | 80 | 1.79 | 1707 |
500 | 37 | 1.68 | 25 | 14 | 80 | 2.11 | 2235 | 4/0 | 19 | 1.40 | 20 | 12 | 80 | 1.82 | 1743 |
500 | 37 | 1.68 | 16 | 12 | 80 | 2.14 | 2285 | 4/0 | 19 | 1.40 | 13 | 10 | 80 | 1.86 | 1805 |
750 | 61 | 1.89 | 24 | 12 | 80 | 2.34 | 2902 | 250 | 37 | 1.45 | 25 | 12 | 80 | 1.88 | 1933 |
750 | 61 | 1.89 | 15 | 10 | 80 | 2.39 | 2963 | 250 | 37 | 1.45 | 16 | 10 | 80 | 1.92 | 1992 |
1000 | 61 | 2.04 | 16 | 9 | 80 | 2.56 | 3560 | 350 | 37 | 1.56 | 32 | 12 | 80 | 2.01 | 2314 |
– | – | – | – | – | – | – | – | 350 | 37 | 1.56 | 20 | 10 | 80 | 2.05 | 2365 |
– | – | – | – | – | – | – | – | 350 | 37 | 1.56 | 16 | 9 | 80 | 2.08 | 2403 |
– | – | – | – | – | – | – | – | 500 | 37 | 1.68 | 29 | 10 | 80 | 2.18 | 2920 |
Wer wir sind China Primary Ud Cable, 35 Kv, Al/Epr/Neutral/LLDPE (AEIC CS 8/ICEA S-94-649) Herstellung und Lieferant,Sie können weitere Informationen per E-Mail erhalten, Sie erhalten einen günstigen Preis oder einen Fabrikpreis.
Get Latest Price Request a quote
Popular 35 kv Produkte
35 kv, XLPE-Isoliert, PVC-Ummantelt, Netzkabel, 1 x 300 mm2
HauptUd Cable, 35 KV, Al/Epr/Neutral/PVC (AEIC CS 8/ICEA S-94-649)
Mv-90, Copper Tape Shield Power Cable, 35 KV, 3/C, Cu/XLPE/Cts/PVC (ICEA S-93-639/NEMA WC71/UL 1072)
HauptUd Cable, 35 KV, Cu/Epr/Neutral/PVC (AEIC CS 8/ICEA S-94-649)
MV-90, Stromkabel für Kupferband, 35 Kv, 3/C, Cu/XLPE/Cts/PVC (ICEA S-93-639/NEMA WC71/UL 1072)
15 kv, 35 kv, 133 %, XLPE-Isoliertes 1-adriges 50 mm2-Netzkabel
Popular Al/Epr/Neutral/LLDPE (AEIC CS 8/ICEA S-94-649) Produkte
Primary Ud Cable, 25 Kv, Al/Epr/Neutral/LLDPE (AEIC CS 8/ICEA S-94-649)
HauptUd Cable, 15 KV, Al/Epr/Neutral/LLDPE (AEIC CS 8/ICEA S-94-649)
Popular boancable Produkte
Na2xsy, Power Cable, 6/10 KV, Al/XLPE/Cws/PVC (HD 620/VDE 0276-620)
Shd-Gaschromatographie, Mining Cable, Cu/Epr/TPU, 3/C, 15kv (ICEA S-75-381/NEMA WC-58) schreiben
Cu/XLPE/Cts/PVC/Sta/PVC, Power Cable, 6/10 (12) KV, 3/C (Iec 60502-2)
Nycwy, Power Cable, 0.6/1 KV, Cu/PVC/Cws/Cts/PVC (Vde 0276-603/HD 603 S1)
Cu/XLPE/PVC, Niederspannungs-Leistung-Kabel, 0.6/1 KV (Iec 60502-1)
HauptUd Cable, 8 KV, Cu/Epr/Neutral/LLDPE (AEIC CS 8/ICEA S-94-649)
Popular Power Cable Produkte
Na2xs2y, Power Cable, 6/10 KV, 1/C, Al/XLPE/Cws/PE (HD 620/VDE 0276-620)
Al/XLPE/Swa/PVC, 0.6/1 Kv, Steel Wire Armored (SWA) Power Cable (IEC 60502-1)
Primary Ud Cable, 25 Kv, Cu/Tr-XLPE/Neutral/LLDPE (AEIC CS 8/ICEA S-94-649)
Nycwy, Power Cable, 0.6/1 KV, Cu/PVC/Cws/Cts/PVC (Vde 0276-603/HD 603 S1)
Cu/XLPE/Cts/Lszh/Awa/Lszh, Power Cable, 6.35/11kv, 1/C (BS 7835)
Tags: 35 kv, Al/Epr/Neutral/LLDPE (AEIC CS 8/ICEA S-94-649), boancable, Power Cable, Primary Ud Cable, Rubber Cable